Features:
1 Single phase or three phase, fits all kinds of power systems.
2 Modular separation structure, easy to install and maintain.
3 Visual indicate window
4 Remote signalling contacted, and remote control
5 Through-flow capacity, low residual depression, fast response time
6 double heat tripping device and temperature control breaking technology
Classified as voltage limiting type SPD, apply to the first protection for the low voltage equipments linked with power line road, to the interference caused by overvoltage, it is installed on LPZ0A -1 or higher interface.
Especially fits for the power box.
type
|
SM-60/3+N
|
SM-40/3+N
|
SM-20/1+N
|
Nominal working voltage
|
380V
|
380V
|
220V
|
Maximum continuous operating voltage(L-N)
|
385V
385V
|
Maximum continuous operating voltage(p-ne)
|
255V
255V
|
Nominal discharge current
|
30kA
|
20kA
|
10kA
|
Max. discharge current
|
60kA
|
40kA
|
20kA
|
Voltage protection level [L-N]Up
|
≤1.95kV
|
≤1.75kV
|
≤1.5kV
|
Voltage protection level [N-PE]Up
|
≤1.5kV
|
≤1.25kV
|
≤1.2kV
|
The response time [L-N]tA
|
≤25ns
|
The response time [N-PE]tA
|
≤100ns
|
Spare fuse
|
160A
|
125 A
|
100A
|
Short-circuit capacity
|
25kA/50Hz
|
Temperature range
|
-40℃…+80℃
|
Install wiring way/ Specification
|
parallel/ flexible16mm2
|
Installation/ Fault Indicator
|
green/ red
|
Enclosure materials
|
red reinforced plastics, UL94-V0
|
Protective level
|
IP20
|
Remote siganl
|
AC:250V/0.5A
|
|